Experimental data for thermal resistance measured on an ETD44 transformer. The temperature rose from 19.7°C to 54.0°C (so change of 34.3°C), with the loss of 3.38W, which gives the thermal resistance of 10.2°C/W. Various sources (e.g. Epcos) give the value for ETD44 between 11 and 12 K/W (see also: thermal resistance of ferrite transformers), so this measurement comes close with the table value.
Data measured by Stan Zurek.